Input terminals: Compact slotted screw terminals (detachable).
Isolation method: Phototriaccoupler.
Zero cross function: Yes.
Operation indicator: Yes.
Alarm output: 2 outputs (Heater Burnout Detection,
SSR Short-circuit Failure Detection).
Applicable load (See note.): 2 to 35 A, 200 to 480 VAC G3PE-525B-3H DC12-24 PDF datasheet.
A New-concept SSR with Built-in.
Current Transformer.
Heater Burnout and SSR Short
G3PE-525B-3H DC12-24
circuit Failure Detection.
Built-in Current Transformer (CT) helps reduce wiring steps.
Detects the burnout of any one of a group of heaters.
Detects the burnout of 3-phase heaters.
Detects SSR short-circuit failures.
Error detection level can be easily set with a switch.
Mounts to a DIN track or with screws G3PE-525B-3H DC12-24 PDF datasheet.
Three types of input terminals available: M3 terminals,
screwless clamp terminals (detachable), or compact slotted,
screw terminals (detachable).
Certified for CSA and EN (TÜV).
The G3PF-2@@B-@@@ Series is UL certified. Refer to Safety Precautions for All Solid State Relays.
Allows 2-wire Switching of 3-phase Power.
Ideal for 2-wire switching of 3-phase heaters.
Improve ease of operation G3PE-525B-3H DC12-24 PDF datasheet. Classification: Input (bifurcated contact), SPST-NO.
Rated voltage: 12 VDC, 24 VDC, 100/110 VAC, 200/220 VAC.
Slim-styled I/O Relay Saves Space in Panel.
SPST-NO, SPST-NC, and SPDT contact forms available for,
output (SPST-NO only for input).
Ultra-slim housing measuring 29 (W) x 10 (D) x 32 (H) mm.
All Output Relays provide a long endurance (1,000,000,
operations at 5 A), while all Input Relays provide microswitching,
power (100 μA at 1 V).
Approved by UL and CSA standards. Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided ffor,
each connector G3PE-525B-3H DC12-24 PDF catalog.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software G3PE-525B-3H DC12-24 PDF catalog.
When setting the nodes with rotary switch,
setting is easy and node identification,