Safety grade (SIL): SIL 3 (IEC 61508).
Performance level (PL): e PL (13849-1 EN/ISO).
Operation control mode: stored procedures repeated operation.
Program capacity: 320K (security program: 40K).
Program memory: 1280K.
Soft element / tag memory: 2306K.
Data memory: 20M.
Integrate security functions into the control system RJ61BT11 PDF datasheet .
Can be used in the previous iQ-R MELSEC series module as a general control purposes,
Use on the same substrate, it can be used to construct a hybrid system with general control and safety control
RJ61BT11
Moreover, IE Field CC-Link network can be integrated with general communication and secure communication,
Ethernet cable can also be used in secure communication,
No need to use a dedicated cable, etc RJ61BT11 PDF datasheet . .
Unified program development environment
Whether the general control procedures or safety control procedures, can be integrated into 1 Engineering documents,
Unified management by Works3 GX. The troublesome operation can save more than one project file management.
When you create a security control program, you are also the same as when you create a general control program,
Various features of GXWorks3 can be developed using the support program RJ61BT11 PDF datasheet . Analog input channel number: 16CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C:-.
Temperature coefficient: positive and negative 35ppm/ MITSUBISHI RJ61BT11 PDF catalog.
Common
Conversion speed: 10ms.
Insulation between channels: isolation transformer insulation.
Absolute maximum input: positive and negative 15V, 30mA MITSUBISHI RJ61BT11 PDF catalog.
External wiring connection: 40 pin connector two.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: DC0 ~ 20mA.
Digital output value: 0 ~ 32000.
Execute event driven program through alarm output
Strengthen the implementation of the interrupt function according to the alarm output flag, easy to carry out preventive maintenance MITSUBISHI RJ61BT11 PDF catalog.
The measured value and the change rate of the analog input signal exceed the upper and lower limits of the set,
Regardless of the procedure of the scan time, can be executed interrupt handling, quickly respond to abnormal conditions.
Analog input module for the external analog signal into the interface of the programmable controller.
Can choose the channel between the insulation, voltage input, current input, voltage / current mixed input, thermocouple input, temperature resiistance (RTD) input for a variety of purposes, such as modules RJ61BT11 datasheet.
Filter high frequency interference.
Analog input module has been equipped with a first order lag filter.
The analog input signal with high frequency interferencee component can be obtained by using the first order lag filter RJ61BT11 PDF datasheet .
Parameters can be set through the filter time constant, no program can be easy to use.