OMRON GX-ID1612 Digital I/O Terminal 3-tier Terminal Block Type GX-ID1612
Brand: OMRON
Name: Digital I/O Terminal 3-tier Terminal Block Type
Model: GX-ID1612
Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance.

Name: Compact Connectors.
Specifications: Outputs; 2 outputs; PNP.
Bit slave of smallest class in industry,
Innovation in wiring for any type of machinery.
Available in 2 types: 2-point Bit Slave Unit,
and 4-point Bit Slave Unit.
Compact size for installation in limited space.
Save space and wiring since bit slave can be,
installed near I/O devices OMRON GX-ID1612.
Industry first bit slave connectable with round,
cables which can be easily purchased at a lower price GX-ID1612
Connectable with flat cables, too for easy wiring.
Cables are selectable depending on applications. Name: CompoNet Gateway Unit for CC-Link.
Specifications: CC-Link Communications,
Specification, Station Type,
Remote device stations;
Number of stations occupied: 4 OMRON GX-ID1612.
CC-Link Version: Version 1.10 or 2.00.
(Selected using mode switch.);
CompoNet Communications Specification,
communications Types of,
Remote I/O Communications;
Maximum I/O capacit, Word Slave Units:
2,048 I/O points total(1,024 inputs and,
1,024 outputs)Bit Slave Units:
512 I/O points total.
(256 inputs and 256 outputs)
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet OMRON GX-ID1612.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site OMRON Digital I/O Terminal 3-tier Terminal Block Type.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error OMRON Digital I/O Terminal 3-tier Terminal Block Type. Name: Temperature Input Units.
Specifications: Thermocouple Input; 4 inputs;
Switchable between.
(R, S, K, J, T, E, B, N, L, U, W, PL2)
Standards: CE, UC, UC1, N .
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet OMRON Digital I/O Terminal 3-tier Terminal Block Type.
Branching is easily made with CompoNet.
Wiring material cosst can be reduced GX-ID1612.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee OMRON GX-ID1612.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.