L60MD4-G-CM MITSUBISHI L60MD4-G-CM Rated output voltage: DC12 ~ 24V Extension cable
Brand: MITSUBISHI
Name: Multiple input (voltage / current / temperature) module
Model: L60MD4-G-CM
Number of input channels: 4ch.
Input voltage: DC - 10 - 10V.
Input current: DC0 ~ 20mA.
Input voltage: 100 ~ 100mV / minute.
Input thermocouple: K, J, T, E, N, R, S, B, U, L, PL II, W5Re/W26Re.
Input temperature resistance: Pt1000, Pt100, JPt100, Pt50.
Conversion speed: 50ms/ch.
Resolution (voltage / current / micro voltage): 1/20000
Resolution (thermocouple): B, R, S, N, PL II, W5Re/W26Re:0.3,, K, E, J, T, U, L:0.1.
Temperature measuring resistance: Pt100, JPt100:0.03, /0.1, Pt1000, Pt50:0.1.
Reduce the programming time.
The digital output value can be easily converted (zoom) to any number of functions without the program.
No need to use ladder diagram conversion program, can reduce the programming time.
Zoom setting example (L60AD4-CM).
The digital output value (20000 ~ 0) of the input range 20mA ~ 4mA is scaled to the value of positive and negative 20000.
Digital filter function
Simply set the parameters, you can eliminate the function of the redundant frequency components.
Can be selected from low pass filter, high pass filter, medium pass filter.
No need to filter the ladder, can reduce programming time.
In addition, the conversion value of the A/D converted by the filter can be obtained at the same time,
Therefore, the total processing time from the conversion to the filter processing can be shortened.

The terminal row is converted to e-CON.Output points: 8 points.
Output form: no public side (all points independent).
Rated output voltage: AC100 ~ 240V.
Max load current: 1A/1 point.
Common way: no public side (all points of independence).
Input / output occupied points: 16 points (I/O distribution: output 16 points) MITSUBISHI L60MD4-G-CM.
External wiring connection: 18 point terminal.
1, the switch quantity acquisition and switch control and RS-485 bus are isolated from each other, and isolated from the whole system L60MD4-G-CM
2, the power supply line has anti reverse connect function, once the wrong power line,
Will automatically cut off the power to protect the entire module is not damaged.
With over-voltage protection function, when the voltage is too high, automatic disconnection,
Protecting the entire module is not damaged MITSUBISHI L60MD4-G-CM.
3, RS-485 interface with 600W lightning protection and surge protection function, with 3000V photoelectric isolation.
4, the use of Modbus protocol, good general, can be very convenient and other systems,
Customers can also according to their own personal needs, custom related agreements, convenient and flexible MITSUBISHI L60MD4-G-CM.
5, communication lines using RS-485 bus, support for multiple modules in parallel use,
Easy to expand the system, good scalability. Cable length: 0.6m.
Weight: 0.19kg.
Definition 1: conductor by one or a plurality of mutually insulated and insulating protective layer made of,
A conductor of electricity or information from one place to another MITSUBISHI Extension cable.
Definition 2: usually by a few or several groups (each with at least two wires) cable rope twisted the similar,
Each group of wires are insulated from each other, and are often twisted around a center,
The entire outer bread has a highly insulated cover MITSUBISHI Extension cable.
The cable has the characteristics of internal power and external insulation MITSUBISHI Extension cable. Number of input channels: 8ch.
Input temperature resistance: Pt1000, Pt100, JPt100, Pt50, Ni500, Ni120, Ni100, Cu100, Cu50.
Conversion speed: 40ms/ch.
Resolution: 0.1.
Status of connected devices by means of alarm monitoring.
Alarm output function
Process alarm.
When the digital value is in the range of preset, the output alarm.
Change rate alarm.
The output value of the output value of the digital output is too large (greater than the rate of change of the alarm limit) or too small (less than the rate of change), the output alarm.
Achieve stability measurement
Inter channel isolation
Isolation between the channels, can prevent the connection of sensors in the channel between the cross talk, so as to achieve stable measurement.
High speed, smooth continuous anaalog output L60MD4-G-CM.
Waveform output function
Equipped with the industry''s first waveform output function.
The pre prepared waveform data can be imported into the analog output module, and the function of the analog output is simulatted according to the set conversion period MITSUBISHI L60MD4-G-CM.
It is not affected by the sequential scan time, and it can realize the high speed and smooth analog output.


...More relevant models >>>>
Last one: LH42C4PT1P-CM
next one: L60AD4-CM