LK Automation Limited LK Automation Limited
Brand: OMRON | MITSUBISHI | Proface | Mennekes | Yaskawa
Go Back >> Product Catalogues
E5AC-QX4ASM-008 Digital temperature controller OMRON E5AC-QX4ASM-008
Brand: OMRON
Name: Digital temperature controller
Model: E5AC-QX4ASM-008
Size: 96 x 96mm.
Control output 1: voltage output (SSR driver).
Control output 2:--.
Auxiliary output: 4 points (auxiliary output 2, 1 common, auxiliary output 3, 4 public general).
Power supply voltage: AC100 ~ 240V.
Terminal shape: screw terminal table type.
Input category: full range multi input.
Heating wire break, SSR fault detection function: 1 points.
Communication: RS-485.
Event input: 2 points.
Remote SP input: -.
Transfer output: -.
Large screen display white PV legible. From selection to setting and operation are simple and easy to use.
Full capacity, function and performance of I/O. Suitable for more applications.
E5AC white LCDPV display height is about 25mm.
The upper panel and the front panel are equipped with tool ports.
With the communication conversion line (sold separately) connected to the computer to establish the controller without the need to install the wire for power supply.
Easy to install CX-Thermo (sold separately).
50ms high speed sampling period.
Model can be equipped with up to 4 point auxiliary output, 6 point event input,
1 point transfer output and remote SP input, suitable for a wide range of applications.
The main body is short, the thickness is only 60mm.
Easy to use programmable logic controller (PLC) is connected to the programmable logic controller (PLC).
The temperature controller is connected to each other by using the component communication.
A new type of proportional control allows you to control the valve.

Size: 1/16 DIN.
Case color: Black.
Power supply voltage: 100 to 240 VAC.
Input type: Analog (current/voltage).
Auxiliary outputs: 2.
Control output 1: Voltage output (for driving SSR).
New 48 x 48-mm Basic Temperature.
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function OMRON E5AC-QX4ASM-008.
Indication Accuracy.
Thermocouple input: ±0 E5AC-QX4ASM-0083% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
New E5CN-U Models (Plug-in Models) with analog inputs and,
current outputs.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV OMRON E5AC-QX4ASM-008.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter. Protection tube diameter: screw pitch W1/4.
Wire length: 4m.
Core line type: K (CA).
Temperature sensing part of temperature controller.
In the application field of packaging molding machine is widely used,
Further strengthened the high cost models OMRON E5AC-QX4ASM-008.
Easy to install / replace the structure.
With springs, you can use the active part (E52Z-CA1D-40). The main body: terminal type, temperature input type.
Category: control output 1 point type (power supply AC100 ~ 240V) OMRON Digital temperature controller.
Shell color: black.
Control output: relay output.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points OMRON Digital temperature controller.
The heater is used to break, SSR fault, heater over current detection function /ES1B power supply: single phase or three phase heater with detection function.
Event input points: -.
Transfer output: -.
Communication: RS-485.
48mm general thermostat has been upgraded & function / performance upgrade OMRON Digital temperature controller.
Indicates that the accuracy is increased and the preventive maintenance function is increased,
Furtheer performance improvement E5AC-QX4ASM-008.
E5CN-U (insert type) add analog input and current output type.
Add PV/SV status display function, convenient to check the state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactivee display PV/SV OMRON E5AC-QX4ASM-008.
Increase the number of control output ON/OFF counting function, can prevent the maintenance of temperature controller internal relay.


...More relevant models >>>>