How does proface write data to MITSUBISHI Q series PLC how to become a multiple of 10? For example, setting 2 on the screen becomes 200 when PLC is monitored., PFXSP5400WAD
Time: 2018/3/18 13:14:12
Where is t PFXSP5400WAD up?
Re: Time: 2018/3/18 22:14:00
Is there PROFACE PFXSP5400WAD decimal PROFACE PFXSP5400WAD number on the screen? Screen direct writing does not support decimal, unless you use a floating point number, or do data conversion