Number of phases: Single-phase.
Insulation method: Phototriac coupler.
Operation indicator: Yes (yellow).
Rated input voltage: 12 to 24 VDC.
Zero cross function: No.
Applicable load: 15 A, 100 to 240 VAC.
Compact, Slim-profile SSRs with Heat,
Sinks. Models with No Zero Cross for,
a Wide Range of Applications OMRON I/O Block PDF datasheet.
RoHS compliant.
Models also available with no zero cross,
Surge pass protection improved surge dielectric strength for,
output currents
G7TC-OC16-1 (OMRON testing).
Compact with a slim profile.
Mount to DIN Track or with screws.
Conforms to UL, CSA, and EN standards (TÜV certification). High-power, Load-control SSRs with.
High Current of 75 or 150 A and High.
Voltage of 240 or 480 VAC OMRON I/O Block PDF datasheet.
RoHS compliant.
Models also available with no zero cross.
Replaceable power elements.
Conforms to cULus standards and EN standards (TÜV certification). Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max.
Input current: 6 OMRON I/O Block PDF datasheet. 0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms) G7TC-OC16-1 PDF datasheet.
Number of circuits per common: 16 inputs/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply G7TC-OC16-1 PDF datasheet.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Short-circuit protection function: No G7TC-OC16-1 PDF datasheet.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit G7TC-OC16-1 PDF catalog. )
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary sswitch and with tool software OMRON I/O Block PDF datasheet.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.