Input capacity: 32 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) OMRON G3RV-SR700-AL DC12 PDF catalog.
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0
G3RV-SR700-AL DC125 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max OMRON G3RV-SR700-AL DC12 PDF catalog.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors OMRON G3RV-SR700-AL DC12 PDF catalog.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Isolation: Phototriac coupler.
Zero cross function: Yes.
Indicator: Yes.
Rated output load: 30 A at 200 to 480 VAC.
Rated input voltage: 12 to 24 VDC.
Extremely Thin Relays Integrated with Heat Sinks.
Downsizing achieved through optimum design of heat sink.
Mounting possible via screws or via DIN track.
Close mounting possible for linking terminals.
(Except for G3PA-260B-VD and G3PA-450B-VD-2.)
Applicable with 3-phase loads.
Replaceable power element cartridges.
Comply with VDE 0160 (finger protection),
with a dielectric strength of 4,000 V between input and load.
Certified by UL, CSA, and VDE (reinforced insulation). Number of phase: Single-phase.
Control terminal block: Screwless clamp terminal block.
Type: Constant current.
Capacity: 45 A, 100 to 240 VAC.
Heater burnout detection: Yes.
Communications: Yes.
High-precision Control with Easy Setup,
Precise heater burnout detection.
Set value and present value monitoring with indicators.
Phase control or optimum cycle control.
RS-485 commmunications to set manipulated variables and,
monitor load current G3RV-SR700-AL DC12 PDF datasheet.
Total run time monitoring.
Output modes for phase control: proportional to phase angle,
proportional to voltage, proportional to square voltage,,
and constant-current control G3RV-SR700-AL DC12 PDF datasheet.
Application with various loads: constant load resistance,
variable load resistance.
UL, and IEC/EN (TÜV) certified.