What case Yaskawa inverter multi speed instruction 1 can not be used
Time: 4/12/2017 9:17:24 AM
The probl Yaskawa inverter that Yaskawa inverter the S5 is chosen as a multi segment speed command 2. This is what causes the frequency of F0, can be the correct choice of frequency instruction can not directly change the.00 and S5, but not the right choice to close the frequency command I found I asked the S5 to set up a multi speed instruction 1
Re: Time: 4/12/2017 10:27:00 PM
The Yaskawa 616G7 inverter for example: to use the S5 terminal, H1-03 parameter is set to 5, the hardware wiring should be connected to S5 terminal of S5, but also set the corresponding parameters in the d1-03 in the frequency value. Check your wiring and parameter settings are correct. Yaskawa G7 inverter multi-function terminal settings: H1-01=3 S3 terminal using S4 terminal for multi speed function H1-02=4 S5 terminal is a multi speed function of H1-03=5 for multi speed function and the D parameters are set as follows: frequency d1-01= frequency value of 1 (corresponding to the S3 terminal frequency) frequency d1-02= frequency value of 2 (corresponding to the S4 terminal frequency) frequency d1-03= frequency value of 3 (corresponding to the S5 terminal frequency) check Yaskawa inverter manual instructions, to prevail.