LK Automation Limited LK Automation Limited
Problem sort: OMRON | MITSUBISHI | Proface | Mennekes | Yaskawa
Home >> Problems
GX Works2 can not open the project, it can not save the project
Time: 4/23/2017 2:43:57 PM

GX Works2d GX Works2 not GX Works2 open the previous project, prompt:
The specified path does not exist in the project file
The project file is read-only or write protected
Insufficient memory space required to open the project
The data of the project file is corrupted
Special symbols are used in the project file name
Prompt when saving a project:
Save target does not exist
Path to the specified drive in the destination
Save target
Re:   Time: 4/24/2017 1:32:00 AM
Do you want to open the project file is also written by the GX Works2 1.531D version of the software saved?
Thank you for your support of MITSUBISHI automation products.
Welcome to call 400-- free technical hotline for further technical information.
Re:Re:   Time: 4/24/2017 3:56:00 AM
He is not only can not open, but also can not save the new project, I am the same, try every means, not good.
Re:Re:Re:   Time: 4/24/2017 8:44:00 AM
You try to create a blank project directly under the test.
Thank you for your support of MITSUBISHI automation products.
Welcome to call 400-- free technical hotline for further technical information.
Re:Re:Re:Re:   Time: 4/24/2017 11:08:00 AM
Modify the registry keys will be as follows:
[HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Control\Lsa\FipsAlgorithmPolicy]
"Enabled" =dword:00000000
Re:Re:Re:Re:Re:   Time: 4/24/2017 3:56:00 PM
All kinds of methods have been tried! Not solve! The key question is that it's always good!
Related problems
Related products
MITSUBISHI
Type DC input module
QX41
MITSUBISHI Type DC input module QX41
Input points: 32 points. Input voltage a
Related download