Master station.
Province distribution network module in cabinet and device.
Link to connect the 64 stations when the fastest scanning time for 1.2ms (rate 2.5Mbps).
According to the transmission distance, the transmission rate is selected from 2.5Mbps, 625kbps and 156kbps.
CC-Link/LT from the station does not need any parameter settings QJ71MES96 User's Manual.
Only need to set up the transmission speed in the master module, you can use the remote I/O
QJ71MES96
QJ61CL12 can be used as the main station of CC-Link/LT.SRAM memory card.
RAM capacity: 2MB. Three-phase 4 wire type.
Measuring circuit number: 3 circuits.
Measurement items: power consumption (consumption, regeneration), current, voltage, power, power factor, etc..
Power measurement module product group capable of simply measuring various energy information QJ71MES96 User's Manual.
With only one module can be used to measure and power consumption (consumption and regeneration), reactive power, current, voltage, power, power factor and frequency of all kinds of detailed information.
No ladder program can continue to monitor the minimum and maximum values, can also perform 2 types of upper / lower limit alarm QJ71MES96 User's Manual.
Only in the ON state can be used to measure the output of the output device.
Therefore, the amount of electricity and the quantity of electricity in the unit of the beat can be obtained during the operation of the equipment.
3 phase 3 wire products can be used to measure up to 4 circuits in one slot,
3 phase 4 wire products can be used to measure up to 3 circuits,
So the electrical energy measurement can be carried out in a small space by the multi circuit products.
For example, a module can be used to measure other loads from the control panel trunk.
In addition, Works2 GX (version 1.90U and higher) can be used to easily set parameters."10BASE-T/100BASE-TX.
Web servo module for RS-232.
Web server module capable of using Internet / Intranet for remote monitoring and operation of programmable controller.
Use the Internet connected to the PC, just through a simple setup,
Remote monitoring / operation of MELSEC from any location.
Data recording function caan be used to display and collect data QJ71MES96 Manual.
Data can be recorded at the shortest distance of 100ms.
Also has the following functions.
Using email to send data / alarm notification.
Using FTP to transfer / access data files.
The display function of event monitor / history record QJ71MES96 Manual.
User authentication /IP filter and other security features.
User can customize the creation of Web pages. "